Gasmaster 1 |
Gasmaster 4 |
Size |
288 x 278 x 110mm (11.3 x 10.9 x 4.3 inches) |
Weight |
4.5kg (10lbs) |
Enclosure material |
Back-box: cast aluminium
Front cover: ABS (flame retardant) |
Ingress protection |
IP65 |
Power |
100-240Vac 50-60Hz or
20-30Vdc, 60W max |
Battery back-up |
1.2Ah batteries fitted internally |
Operating temperature |
-10°C to +50°C (14°F to +122°F) |
Inputs |
Gas One 2 or 3 wire 4-20mA gas detector (sink or source) or mV pellistor flammable gas detector |
One to four 2 or 3 wire 4-20mA gas detectors (sink or source) or mV pellistor flammable gas detectors |
|
Fire One loop of up to 20 conventional smoke/heat detectors or manual call points, or one flame detector (4-20mA or digital contact signal) |
One to four loops of up to 20 conventional smoke/heat detectors or manual call points, or one to four flame detectors |
|
ESU For use with one Crowcon ESU fan |
|
Remote inhibit/retest Via normally open contact |
Outputs |
Relays DPCO contacts rated 250Vac 8A
Low alarm. High alarm. Fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms |
Low alarm and high alarm per channel plus common low, high and fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms |
|
A/V alarm drive 12Vdc or 24Vdc 650mA max. drive. Suitable for +ve or -ve switched alarms |
|
Analogue 4-20mA (current source, max. loop resistance 700?) or 1-5Vdc (min. load 50k? ) |
4-20mA for each channel (current source, max. loop resistance 700?) or 1-5Vdc (min. load 50k?) |
|
Serial link RS-485 Modbus RTU for monitoring and control via DCS/SCADA/PLC systems |
Communications port |
Optional port for PC configuration and event log upload |
Event logging* |
Time-stamped log of up to 300 alarms, fault or system intervention activities |
Panel indication |
LCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alpha-numeric status indication.
LED’s for Alarm, Fault, Power and Warning. Integral 85dB sounder (at 10cm) |
Approvals |
EMC: EN50270, EN60945, FCC Part 15, ICES002
ATEX: EN60079-25:2010 |
Functional safety |
Validated to IEC61508
SIL2 |